1. Option Unit is necessary when:
a. MASTER does not built-in
RS485 har dware
b. MASTER does not
support Modbus(RTU) Protocol
2. Maximum Drive N is determined by:
a. N=99, shen master can assign multiple ID address
b. N=8, when master
can assign only 1 ID address(etc. HMI)
3. Only PDS and PD an series support Modbus(RTU)
protocol
..............................................
How to connect to Easyview-HMI
RS485(RS422) port to PDS inverter
D-sub
9pin Male<-->JAM-SC-5P
Pin4←---------------------→ Sig + Pin3(A)
Pin5←---------------------→ Sig - Pin4(B)
Pin6←---------------------→ 0V Pin2(0V)
...................................................................
How to connect to Easyview-HMI RS232
port to JPS(232/485) comm. board
D-sub
9pin Male<-->D-sub 9pin Female
Pin2←---------------------→ Pin3
Pin3←---------------------→ Pin2
Pin5←---------------------→ Pin5(GND)
Pin7←---------------------→ Pin8
Pin8←---------------------→ Pin7
.....................................................................
How to connect to Proface-HMI RS485
port to PDS inverter
D-sub
25pin Male←---------------------------------------→JAM-SC-5P
Pin4← →Pin5
Pin7----------------------------------------------------------→ 0V Pin2(JAM)
Pin9← →Pin10← →Pin11----------------------------→Sig+ Pin3(JAM)
Pin15← →Pin16----------------------------------------→Sig- Pin4(JAM)
Pin18← →Pin19
Pin21← →Pin22
.....................................................................
How to connect PC 9-Pin Communication port to PDA/E
communication board
PC 9-Pin
PDA/E Com. Board
Pin1: N.C.
Pin2: RX to RX
Pin3: TX to TX
Pin4: N.C.
Pin5: 0V to 0V
Pin6: DSR to 9V
Pin7: RTS to RTS
Pin8: CTS to 9V
Pin9: N.C.